EUROPEANSTANDARDEN50676
EUROP?ISCHENORMDecember2019
ICS13.320;27.200
EnglishVersion
Electricalequipmentusedfordetectionandconcentration
measurementofrefrigerantgases-Performancerequirements
andtestmethods
Appareilsélectriquesutilisespourladétectionetlamesure
delaconcentrationdegazfrigorigènes-Exigencesde
performanceetméthodesd'essai
ElektrischeGer?tezurDetektionunud
KonzentrationsmessungvonK?ltemittelgasen-
AnforderungenandasBetriebsverhaltenundPrüfverfahren
ThisEuropeanStandardwasapprovedbyCENELECon2019-11-04.CENELECmembersareboundtocomplywiththeCEN/CENELEC
InternalRegulationswhichstipulatetheconditionsforgivingthisEuropeanStandardthestatusofanationalstandardwithoutanyalteration.
Up-to-datelistsandbibliographicalreferencesconcerningsuchnationalstandardsmaybeobtainedonapplicationtotheCEN-CENELECManagementCentreortoanyCENELECmember.
ThisEuropeanStandardexistsinthreeofficialversions(English,French,German).AversioninanyotherlanguagemadebytranslationundertheresponsibilityofaCENELECmemberintoitsownlanguageandnotifiedtotheCEN-CENELECManagementCentrehasthesamestatusastheofficialversions.
CENELECmembersarethenationalelectrotechnicalcommitteesofAustria,Belgium,Bulgaria,Croatia,Cyprus,theCzechRepublic,Denmark,Estonia,Finland,France,Germany,Greece,Hungary,lceland,Ireland,Italy,Latvia,Lithuania,Luxembourg,Malta,the
Netherlands,Norway,Poland,Portugal,RepublicofNorthMacedonia,Romania,Serbia,Slovakia,Slovenia,Spain,Sweden,Switzerland,TurkeyandtheUnitedKingdom.
EuropeanCommitteeforElectrotechnicalStandardizationComitéEuropeendeNormalisationElectrotechnique
Europ?ischesKomiteefürElektrotechnischeNormung
CEN-CENELECManagementCentre:RuedelaScience23,B-1040Brussels
◎2019CENELECllrightsofexploitationinanyformandbyanymeansreservedworldwideforCENELECMembers.
Ref.No.EN50676:2019E
2
EN50676:2019(E)
ContentsPage
Europeanforeword 3
Introduction 3
1Scope 5
2Normativereferences 5
3Termsanddefinition 6
Figure1—Warm-uptimeincleanair(typical) 8
4Generalrequirements 8
4.1Introduction 8
4.2Construction 9
Table1—Measuringranges,referencevaluesandmaximumthreshold 9
4.3Adjustments 10
4.4Gasdetectiontransmitterforusewithseparategasdetectioncontrolunits 10
4.5Separategasdetectioncontrolunitsforusewithgasdetectiontransmitter(s.) 10
4.6Equipmentusingsoftwareand/ordigitaltechnologies 10
4.7Labellingandmarking 10
4.8Instructionmanual 11
5Testmethods 11
5.1Introduction 11
5.2Generalrequirementsfortest 1
5.3Samplesandsequenceoftest 1
5.4Normalconditionsfortest 12
5.5Tests 13
Table2—Testgasforpoisongastes 15
AnnexA(normative)Gasspecificperformancerequirements(EN45544-1) 17
TableA.1—Gasspecificperformancerequirement 17
AnnexB(normative)Performancerequirementsunderstandardtestcondition 18
TableB.1—Performancerequirementsunderstandardtestcondition 18
Bibliograph 20
EN50676:2019(E)
3
Europeanforeword
Thisdocument(EN50676:2019)hasbeenpreparedbyCLC/TC216"Gasdetectors".
Thefollowingdatesarefixed:
·latestdatebywhichthisdocumenthas(dop)2020-11-04
tobeimplementedatnationallevelby
publicationofanidenticalnational
standardorbyendorsement
latestdatebywhichthenational((dow)2022-11-04
standardsconflictingwiththisdocument
havetobewithdrawn
Attentionisdrawntothepossibilitythatsomeoftheelementsofthisdocumentmaybethesubjectofpatentrights.CENELECshallnotbeheldresponsibleforidentifyinganyorallsuchpatentrights.
EN50676:2019(E)
4
Introduction
ThisdocumentspecifiestestmethodsandperformancerequirementsforallelectricalequipmentusedforgasdetectioninrefrigerantapplicationsasdefinedinEN378-1:2016bymeansofconcentrationmeasurement.
Thisdocumentisaddressedtothemanufacturersofsuchequipmentandtestlaboratorieswhichvalidateit.Thetendencytouselow-GWPrefrigerantgasesintherefrigerationandHVACmarket(F-GasRegulation)hasintensifiedtheconsiderationsofsafetymeasuresforlow-GWPgasesassomeareflammable,toxicandcancauselackofoxygen.
Thisdocumentcoversallrefrigerantgasesanddefinesperformancerequirementsforthedetectionequipment,mentionedinEN378-3:2016asgasdetectorsorsensors,usedinrefrigerantapplications.Thelevelofsafetyisexpectedtobethesameasinthealreadyexistingperformancestandardsforgeneral-purposeequipment,i.e.EN60079-29-1concerningrefrigerantflammablegasesandEN45544seriesconcerningrefrigeranttoxicgasesinatmospheres.RefrigerantgasesnotmentionedbyEN378-1:2016are
alsocoveredbythisstandardfollowingthecategorizationschemeofEN378-1:2016.
EN50676:2019(E)
5
1Scope
Thisdocumentspecifiesgeneralrequirementsfortheconstruction,testingandperformanceofelectricallyoperatedrefrigerantfixedgasdetectionequipmentinsafetyapplications.ThisdocumentdoesnotspecifyrequirementsforportablelocatingleakdetectorsforrefrigerantapplicationasalreadycoveredbyEN14624:2012.
Thisdocumentisapplicabletoequipmentwhoseprimarypurposeistoprovideanindication,alarmand/orotheroutputfunctiontowarnofthepresenceofrefrigerantgasesinanindustrialorcommercialenvironmentand,insomecases,toinitiateautomaticormanualprotectiveactions.Itisapplicabletoequipmentinwhichthesensorautomaticallygeneratesanelectricalsignalwhengasispresent.
Thisstandarddoesnotapplytogasdetectionequipment:
一fornon-refrigerantapplication;
一usedforairpollutionmonitoring;
一samplingsystems,whicharenotintegralpartofthegasdetectionequipment;
一openpathgasdetection;
一residentialapplications;—processcontrol;
一forapplicationsinmines;
一portablelocatingleakdetectorsforrefrigerantapplication.
2Normativereferences
Thefollowingdocumentsarereferredtointhetextinsuchawaythatsomeoralloftheircontentconstitutesrequirementsofthisdocument.Fordatedreferences,onlytheeditioncitedapplies.Forundatedreferences,thelatesteditionofthereferenceddocument(includinganyamendments)applies.
EN378-1:2016,Refrigeratingsystemsandheatpumps-Safetyandenvironmentalrequirements-Part1:Basicrequirements,definitions,classificationandselectioncriteria
EN45544-1,Workplaceatmospheres-Electricalapparatususedforthedirectdetectionanddirectconcentrationmeasurementoftoxicgasesandvapours-Part1:Generalrequirementsandtestmethods
EN45544-2,Workplaceatmospheres-Electricalapparatususedforthedirectdetectionanddirectconcentrationmeasurementoftoxicgasesandvapours-Part2:Performancerequirementsforapparatususedforexposuremeasurement
EN45544-3,Workplaceatmospheres-Electricalapparatususedforthedirectdetectionanddirectconcentrationmeasurementoftoxicgasesandvapours-Part3:Performancerequirementsforapparatususedforgeneralgasdetection
EN45544-4,Workplaceatmospheres-Electricalapparatususedforthedirectdetectionanddirectconcentrationmeasurementoftoxicgasesandvapours-Part4:Guideforselection,installation,useandmaintenance
EN60079-29-1:2016,Explosiveatmospheres-Part29-1:Gasdetectors-Performancerequirementsofdetectorsforflammablegases
IEC60335-2-40,Householdandsimilarelectricalappliances-Safety-Part2-40:Particularrequirementsforelectricalheatpumps,air-conditionersanddehumidifiers
EN50676:2019(E)
6
Forthepurposesofthisdocument,thetermsanddefinitionsgiveninEN60079-29-1,EN45544seriesandthefollowingapply.
ISOandIECmaintainterminologicaldatabasesforuseinstandardizationatthefollowingaddresses:
·IECElectropedia:availableat
/
·ISOOnlinebrowsingplatform:availableat
/obp
3.1Gasproperties
3.1.1
refrigerant
fluidusedforheattransferinarefrigeratingsystem,whichabsorbsheatatalowtemperatureandalowfluidpressureandexpelsheatatahighertemperatureandahigherpressureusuallyinvolvingchangesofthestateofthefluid
3.1.2
halocarbonandhydrocarbon
either:
—CFC:fully-halogenatedhalocarboncontainingonlychlorine,fluorineandcarbon;
一HCFC:halocarboncontaininghydrogen,chlorine,fluorineandcarbon;
一HFC:halocarboncontainingonlyhydrogen,fluorineandcarbon;
—PFC:fullyfluorinatedhalocarboncontainingonlyfluorineandcarbon;
一HC:hydrocarboncontainingonlyhydrogenandcarbon[SOURCE:EN378-1:2016,3.7.14]
3.1.3
hydrocarbon
containsonlyhydrogenandcarbon
3.1.4
globalwarmingpotential
GWP
climaticwarmingpotentialofagreenhousegasrelativetothatofcarbondioxide(CO2'),calculatedintermsofthe100-yearwarmingpotentialofonekilogramofagreenhousegasrelativetoonekilogramofCO2
3.1.5
poison
poisonforsensors
substancewhichleadstotemporaryorpermanentlossofsensorsensitivity
3.1.6
referencevalue
valueusedasthebasistospecifyrequirementssuchasmeasuringrange,resolutionandalarmsetpoint
3.1.7
measuringrange
rangeofmeasuredvaluesofgasconcentrationoverwhichtheaccuracyoftheequipmentlieswithinspecifiedlimits
EN50676:2019(E)
7
groupofgases
definedbythemanufacturertobemeasuredwithonepieceofequipmentwithoutmodificationofhardwareorsoftwarewhichcanberepresentedbyareferencegasalsodefinedbythemanufacturer
3.1.9
referencegas
representativegasofagroupofgases
Note1toentry:Onlythereferencegasisspecificallytestedincorrespondencewiththeperformancerequirementsofthispresentstandard.
3.1.10
correctionfactor
factordefinedbythemanufacturertoconvertthemeasurementvaluesofagivengasfromagroupinrelationtothedefinedreferencegas
3.1.11
acute-toxicityexposurelimit
ATEL
maximumrecommendedrefrigerantconcentrationdeterminedinaccordancewithEN378-1andintendedtoreducetherisksofacutetoxichazardstohumansintheeventofarefrigerantrelease
[SOURCE:EN378-1:2016,3.7.5,modified]
3.1.12
occupationalexposurelimitvalue
OELV
limitofthetime-weightedaverageoftheconcentrationofachemicalagentintheairwithinthebreathingzoneofaworkerinrelationtoaspecifiedreferenceperiod
Note1toentry:Theterm“"limitvalue”isoftenusedasasynonymfor“occupationalexposurelimitvalue”,buttheterm“occupationalexposurelimitvalue”ispreferredbecausethereismorethanonelimitvalue(e.g.,biologicallimitvalueandoccupationalexposurelimitvalue).
Note2toentry:Occupationalexposurelimitvalues(OELVs)areoftensetforreferenceperiodsof8h,butcanalsobesetforshorterperiodsorconcentrationexcursions.
3.1.13
machineryroom
spacethatisdesignedtohousecompressorsandpressurevessels
3.2Typesofequipmentandcomponents
3.2.1
gasdetectiontransmitter
fixedgasdetectionequipmentthatprovidesaconditionedelectronicsignaloroutputindicationtoagenerallyacceptedindustrystandard(suchas4mAto20mA),intendedtobeutilizedwithseparategasdetectioncontrolunitsorsignalprocessingdataacquisition,centralmonitoringandsimilarsystems,andwhichtypicallyprocessesinformationfromvariouslocationsandsourcesincluding,butnotlimitedtogasdetectionequipment
3.2.2
alarm-onlyequipment
equipmenthavinganalarmbutnotadisplayorotherdevicetoindicatethemeasuredgasconcentration
Note1toentry:InEN14624andEN378-3,thistypeofelectricalequipmentisdefinedasanindicatingfixedgasdetector.
EN50676:2019(E)
8
3.3.1
timeofresponse
tx
timeinterval,whentheequipmentisinawarmed-upcondition,betweenthetimewhenaninstantaneousvariationinvolumeratioisproducedattheequipmentinletandthetimewhentheresponsereachesastatedpercentage(x)ofthefinalindication
Note1toentry:Thisdocumentreferslot90asthetimeofresponse.
3.3.2
warm-uptime
timeinterval,withtheequipmentinastatedatmosphere,betweenthetimewhentheequipmentisswitched
onandthetimewhentheindicationreachesandremainswithinthestatedtolerancesNote1toentry:ForanexampleseeFigure1.
Note2toentry:Warm-uptimeisnotapplicabletospot-readingequipment.
Key
1poweroffincleanair
2poweronincleanair
3apparatuszero
4specifiedtolerancebandonzeroindication
5warm-uptimeyindication
Xtime
Figure1—Warm-uptimeincleanair(typical)
4Generalrequirements
4.1Introduction
一TypeI:RefrigerantgasdetectionequipmentforA2,A2L,A3,B3refrigerantsandammonia(R717)aspersafetyclassinEN378-1:2016,AnnexEinaccordancewithexplosionprotection.TheequipmentshallfollowtheexistingperformancesinEN60079-29-1forrangesupto20%LFLandor0%-100%LFL.andperformancerequirementsinEN378series
EquipmentshallfulfilthegeneralrequirementsofEN60079-29-1andthethresholdsspecifiedinEN378series.
EN50676:2019(E)
9
AnnexEofEN378-1:2016.PerformanceoftheequipmentshallbeinaccordancewithgeneralrequirementsinEN45544-1incombinationwithEN45544-2.andsuitableforexposuremeasurementsinworkplaceatmospheres.
EquipmentshallfulfilthegeneralrequirementsofEN45544-1inconjunctionwithEN45544-2.
一TypeII:RefrigerantgasdetectionequipmentforA1,A2L,B1,B2LrefrigerantsaspersafetyclassinAnnexEofEN378-1:2016notcoveredbyTypelorTypeII.PerformanceoftheequipmentshallbeinaccordancewithgeneralrequirementsinEN45544-1incombinationwithEN45544-3andEN378series.
EquipmentshallfulfilthegeneralrequirementsofEN45544-1inconjunctionwithEN45544-3andthethresholdsspecifiedinEN378series.
Followingextensionsanddeviationsfromthesegeneralrequirementsareapplicable.
4.2Construction
4.2.1General
EN60079-29-1andEN45544seriesshallapply.
4.2.2Measuringrangesandcorrectionfactor
General
ThemaximummeasuringrangeforTypeIandTypeⅢlequipmentorthereferencevalueforTypelequipmentforeachgastobemeasuredshallbeasspecifiedinTable1.
Ifareferencegasisspecifiedforagroupofgasestherelatedcorrectionfactorshallnotexceedthelimitsofmin.0,25tomax.4.
EquipmentshallcomplytothemaximumthresholdsspecifiedintheEN378series.
ForapplicationscoveredbyF-GasDirective(F-GasEU-51712014)therangeandthethresholdsshallbereferencedfromtheNationalStandards.
Table1—Measuringranges,referencevaluesandmaximumalarmthresholds
Typel
Typell
TypeI
Maximum
alarm
thresholdsa
Gas
Measuringrange
RefrigerantgasdetectionequipmentforA2,A2L,R717,A3,B3refrigerantgasesshall
followEN60079-29-1
Referencevalue
Refrigerantgas
detectionequipmentforA1,A2L,B1,B2L
shallfollowEN45544-2
Measuringrange
Refrigerantgasdetection
equipmentforA1,A2L,B1,B2L
notcoveredbytypelorllshall
followEN45544-3
EN378series
IEC60335-2-40
HC
Hydrocarbons
0%-100%LEL
0%-20%LEL
-
<25%LEL
Ammonia
0%-100%LEL
(0-150000ppm)
0%-20%LEL
(0-30000ppm)
20ppm
0ppm-5000ppm
Pre-set
<500ppm
Mainalarm
<30,000ppm
(<20%LEL)
EN50676:2019(E)
10
Typel
Typell
TypeⅢll
Maximum
alarm
thresholdsa
Carbon
Dioxide
5000ppm
0ppm-50000ppm
Halogenated
0%-100%LL
0%-20%LEL
0ppm-5000ppm
aAlarmvalue(threshold)shallbesetbelowthevaluereportedinthecolumn,asreferencetotheStandardsmentioned
Selectablerange
EN60079-29-1andEN45544seriesandthresholdsasEN378seriesshallapply.
4.2.3Alarmsignal
EN60079-29-1andEN45544seriesshallapply
4.2.4Faultsignal
EN60079-29-1andEN45544seriesshallapply.
4.3Adjustments
EN60079-29-1andEN45544seriesshallapply.
4.4Gasdetectiontransmitterforusewithseparategasdetectioncontrolunits
EN60079-29-1andEN45544-1shallapply.
4.5Separategasdetectioncontrolunitsforusewithgasdetectiontransmitter(s)
EN60079-29-1andEN45544-1shallapply.
4.6Equipmentusingsoftwareand/ordigitaltechnologies
EN60079-29-1andEN45544seriesshallapply.
4.7Labellingandmarking
4.7.1General
EN60079-29-1andEN45544seriesshallapply
Theequipmentshallbemarkedlegiblyandindeliblyadditionalwith:
一“EN"inconjunctionwith“50676”forthecontrolunitsand"EN”inconjunctionwith“50676”,followedbyTypeI,TypellorTypeII(torepresentconformitywiththisstandard)forgasdetectors.
4.7.2Typesandelectricalprotection
General
EN60079-29-1andEN45544seriesshallapply.
Displayandotherdevicesforindicationofmeasuredvalues
EN60079-29-1andEN45544seriesshallapply.
EN50676:2019(E)
11
EN60079-29-1andEN45544seriesshallapply.
Indicatorlight
EN60079-29-1andEN45544seriesshallapply.
4.8Instructionmanual
EN60079-29-1andEN45544seriesshallapply.
Eachpieceofequipmentshallbeprovidedwithaninstructionmanualthatincludealladditionalinstructions,drawingsanddiagramsforsafeandproperinstallation,commissioning,operation,maintenanceanddecommissioningoftheequipmentincludinganyinformationforuseofequipmentasaTypel,Typelland/orTypeIlinrefrigerantapplications.
Additionalinformationthatdescribesthesensitivities(andvariabilityofsensitivity)toothergasestowhichtheequipmentisresponsiveshallbeaddedandalsothereferencegasandthecorrectionfactorsifclaimedoneasrepresentativeofagroupofgases.
Explicitrestrictionofthetemperaturerangeto-20℃foranyequipmentwhichhasnotbetestedforverylowtemperatureapplicationsaccordingto5.5.6.
5Testmethods
5.1Introduction
TypeIequipmentshallbesubjectedtothetestmethodsandacceptancecriteriadescribedinEN60079-29-1.
ForTypelequipmentforammoniawithmeasuringrangesupto20%LELitshallbesufficienttomeettheperformancerequirementsforequipmentwithmeasuringrangesupto100%LEL.Acceptancecriteriashallbecalculatedwiththevalue100%LELforthemeasuringrange.
TypellequipmentshallbesubjectedtothetestmethodsandacceptancecriteriadescribedinEN45544-1inconjunctionwithEN45544-2.
TypeIlequipmentshallbesubjectedtothetestmethodsandacceptancecriteriadescribedinEN45544-1inconjunctionwithEN45544-3.
5.2Generalrequirementsfortests
EN60079-29-1andEN45544seriesshallapply.
Deviationsoftheperformancerequirementsshallbereportedintheinstructionmanualclearly
5.3Samplesandsequenceoftests
5.3.1Testsamples
EN60079-29-1andEN45544seriesshallapply.
5.3.2Sequence
EN60079-29-1andEN45544seriesshallapply.
5.3.3Gasdetectiontransmitters
EN60079-29-1andEN45544seriesshallapply.
5.3.4Separatecontrolunits
EN60079-29-1andEN45544seriesshallapply.
EN50676:2019(E)
12
EN60079-29-1andEN45544seriesshallapply.
5.3.6Maskforcalibrationandtest
5.4Normalconditionsfortest
5.4.1General
EN60079-29-1andEN45544seriesshallapply.
5.4.2Testgas(es)
EN60079-29-1andEN45544seriesshallapply.
5.4.3Standardtestgas
EN60079-29-1andEN45544seriesshallapply.
Ifthemanufacturerclaimstocoveragroupofgasesthereferencegasmentionedshallbeusedasstandardtestgas.
5.4.4Flowratefortestgases
EN60079-29-1andEN45544seriesshallapply.
5.4.5Powersupply
EN60079-29-1andEN45544seriesshallapply.
5.4.6Temperature
EN60079-29-1andEN45544seriesshallapply.
5.4.7Pressure
EN60079-29-1andEN45544seriesshallapply.
The120kPapressurelevelmaybeomittediftheinstructionmanualspecifiesthatequipmentisnotintendedforuseforabove110kPapressurelevel.
Forbelowgroundapplicationsthepressurelevelmayexceed110kPa
5.4.8Humidity
EN60079-29-1andEN45544seriesshallapply.
5.4.9Acclimationtime
Ineachinstancewheretheequipmentissubjectedtoadifferenttestcondition,theequipmentshallbeallowedtoacclimatizeunderthesenewconditionsbeforemeasurementsaretaken.
EN60079-29-1andEN45544seriesshallapply.
5.4.10Orientation
Theequipmentshallbetestedintheorientationrecommendedintheinstructionmanual.
EN60079-29-1andEN45544seriesshallapply.
5.4.11Communicationsoptions
Forequipmenthavingcommunicationsoptionsusedduringnormalgasdetectionoperation,testin5.5.3,5.5.9and5.5.18shallbeperformedwithallcommunicationportsconnected.Themaximumtransactionrate,cablingcharacteristicsandactivitylevelspecifiedintheinstructionmanualshallbeemployed.
EN60079-29-1andEN45544seriesshallapply.
EN50676:2019(E)
13
Forgasdetectionequipment,whicharepartofsystems,testsin5.5.3,5.5.9,5.5.18,5.5.19andPowersupplyvariationsshallbeperformedwiththemaximumsystemcommunicationstransactionrateandactivitylevel.Thisshallcorrespondtothelargestandmostcomplexsystemconfigurationpermittedbytheinstructionmanual.
EN60079-29-1andEN45544seriesshallapply.
5.5Tests
5.5.1General
EN60079-29-1andEN45544seriesshallapply.
5.5.2Unpoweredstorage
EN60079-29-1andEN45544seriesshallapply.
5.5.3Calibrationandadjustment
Introduction
EN60079-29-1andEN45544seriesshallapply.
Calibrationcurve
Ifthemanufacturerclaimstocoveragroupofgasesthistestshallbeperformedwithallgasesofthegroup.Fromthemeasurementsforeachgasthecorrectionfactorsaccordingtothereferencegasshallbecalculatedusingforeachcalibrationcurve:anykindoftransferfunction,accordingtothemanufacturerinstructions.
Additionalacceptancecriteria:EN60079-29-1andEN45544shallapplyforeachgasandcorrectionfactorshallbebetween0,25and4.
Responsetodifferentgases
EN60079-29-1andEN45544seriesshallapply.
Ifthemanufacturerclaimstocoveragroupofgasesthistestshallbeperformedwithallgasesofthegroup.Theratiobetweentheindicationoftheequipment(beforecorrectionusingthemanufacturer'sresponsecorrectionfactors)andthegasvolumefractionobtainedforeachofthethreegasvolumefractionsofeachgastestedshallnotbelessthan0,25andshallnotexceed4,0.
5.5.4Stability
EN60079-29-1andEN45544seriesshallapply.
5.5.5Alarmsetpoint(s)
General
EN60079-29-1andEN45544seriesshallapply.
Lowvoltageandpowerinterruption
EN60079-29-1andEN45544seriesshallapply.
Fieldwiringfaults
.1General
EN60079-29-1andEN45544seriesshallapply.
EN50676:2019(E)
14
EN60079-29-1andEN45544seriesshallapply.
Sensordisconnection
EN60079-29-1andEN45544seriesshallapply.
AutomaticallyAspiratedEquipmentEN60079-29-1andEN45544seriesshallapply.
5.5.6Temperature
EN60079-29-1andEN45544seriesshallapply.
Equipmentdesignedforapplicationsatextendedlowtemperaturelevels(below-20℃)shallbetestedat-40℃additional.
Deviationsoftheperformancerequirementsshallbereportedintheinstructionmanualclearly.
5.5.7Pressure
EN60079-29-1andEN45544seriesshallapply.
Notapplicable.SeeNote5.4.7
5.5.8Humidityoftestgas
EN60079-29-1andEN45544seriesshallapply.
5.5.9Airvelocity
Notapplicable
5.5.10Flowrateforaspiratedequipment
EN60079-29-1andEN45544seriesshallapply.
5.5.11Orientation
EN60079-29-1andEN45544seriesshallapply.
5.5.12Vibration
EN60079-29-1andEN45544seriesshallapply.
5.5.13Warm-uptime
EN60079-29-1andEN45544seriesshallapply.
5.5.14Timeofresponse
EN60079-29-1andEN45544seriesshallapply.
ForTypeⅢ≤requirementsTableA1.ForothergasesnotinTableA.1,t(50)inlessthan60st(90)inlessthan150swithaprobe:+3spermetre
5.5.15Timeofrecovery
Notapplicable
5.5.16Highgasconcentrationoperationabovethemeasuringrange
EN60079-29-1andEN45544seriesshallapply.
EN50676:2019(E)
15
EN60079-29-1andEN45544seriesshallapply.
5.5.18Electricaltests
EN60079-29-1andEN45544seriesshallapply.
5.5.19Fieldcalibrationkit
EN60079-29-1andEN45544seriesshallapply.
5.5.20Verificationofsoftwareanddigitalcomponents
EN60079-29-1:2016,4.9,andEN45544seriesshallapply.
5.5.21Resistantagainstpoisoningeffectstothesensorbythegastobemeasure
Table2—Testgasforthepoisongastest
Measurement
technology
HC
ChlorinatedorbromatedorfluorinatedHCs
Infra-red
not
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。
最新文檔
- 重堿煅燒工安全知識(shí)評(píng)優(yōu)考核試卷含答案
- 橋涵養(yǎng)護(hù)培訓(xùn)教材
- 橋梁建設(shè)安全培訓(xùn)教材
- 橋式起重機(jī)吊鉤培訓(xùn)課件
- 酒店客房維修保養(yǎng)制度
- 酒店餐飲部食品安全與食品安全培訓(xùn)制度
- 超市商品銷售及庫存管理制度
- 濟(jì)源培訓(xùn)班教學(xué)課件
- 流感傳染病培訓(xùn)
- 2024-2025學(xué)年山西省運(yùn)城市高一下學(xué)期期末考試歷史試題(解析版)
- 胰腺常見囊性腫瘤的CT診斷
- 房屋尾款交付合同(標(biāo)準(zhǔn)版)
- 檢測(cè)設(shè)備集成優(yōu)化方案
- 2025數(shù)據(jù)中心液冷系統(tǒng)技術(shù)規(guī)程
- 2021-2025年河南省中考英語試題分類匯編:短文選詞填空(學(xué)生版)
- 2025年江蘇醫(yī)藥行業(yè)分析報(bào)告及未來發(fā)展趨勢(shì)預(yù)測(cè)
- 腫瘤內(nèi)科知識(shí)培訓(xùn)內(nèi)容課件
- 電化學(xué)儲(chǔ)能電站火災(zāi)成因多維度分析及消防安全體系現(xiàn)狀與對(duì)策研究
- 物業(yè)安全部工作年終總結(jié)
- 起重吊裝應(yīng)急演練
- IPC7711C7721C-2017(CN)電子組件的返工修改和維修(完整版)
評(píng)論
0/150
提交評(píng)論