防排煙前室、樓梯間加壓送風(fēng)量計(jì)算表,,,,,,,,,,,,,,,,,,,,"★取值說(shuō)明:

●v-門(mén)洞斷面風(fēng)速;樓梯間、前室均送風(fēng)0.7m/s;樓梯間送風(fēng),獨(dú)立前室不送風(fēng)1.0m/s;消防電梯前室送風(fēng)1.0m/s;樓梯間自然通風(fēng),前室送風(fēng)0.6(樓梯間門(mén)總面積/前室門(mén)總面積+1)m/s;

●△P-漏風(fēng)門(mén)平均壓差;0.7m/s時(shí),6.0Pa;1.0m/s時(shí),12Pa;1.2m/s時(shí),17Pa;

●N1-疏散門(mén)開(kāi)啟數(shù)量;樓梯間:24m以下,2層內(nèi)疏散門(mén)開(kāi)啟,取2;24m以上,3層內(nèi)疏散門(mén)開(kāi)啟,取3;地下樓梯間,1層內(nèi)疏散門(mén)開(kāi)啟,取1;前室,取3,<3層的按實(shí)際層數(shù)??;

●N2-漏風(fēng)門(mén)數(shù)量;加壓樓梯間總門(mén)數(shù)-N1;

●N3-漏風(fēng)閥門(mén)數(shù)量;前室樓層數(shù)-3;

●A-單個(gè)門(mén)漏風(fēng)面積;1.5m*2.0m,0.018m2;1.2m*2.0m,0.0168m2;1.2m*2.0m,0.012m2",,,

系統(tǒng)編號(hào),消防加壓送風(fēng)部位,,前室送風(fēng)量,樓梯間送風(fēng)量,門(mén)縫面積,平均壓差,漏風(fēng)門(mén)數(shù)量,門(mén)縫漏風(fēng)量,門(mén)洞面積,門(mén)洞風(fēng)速,開(kāi)啟門(mén)數(shù),門(mén)洞送風(fēng)量,閥門(mén)面積,漏風(fēng)閥門(mén)數(shù)量,閥門(mén)漏風(fēng)量,計(jì)算風(fēng)量,風(fēng)道截面,風(fēng)口截面,設(shè)計(jì)風(fēng)量,,,,

,層數(shù),部位,Ls=L1+L3(m3/h),Lj=L1+L2(m3/h),A,△P,N2,L2,Ak,v,N1,L1,AF,N3,L3,,按15m/s,按5m/s,,,,,

,,,,,(㎡),(Pa),(個(gè)),(m3/s),(㎡),(m/s),(個(gè)),(m3/s),(㎡),(個(gè)),(m3/s),(m3/h),(㎡),(㎡),(m3/h),,,,

,1,合用前室(1個(gè)門(mén)),8100,,,,,,3.2,0.70,1,2.24,0.45,0,0.00,8100,0.15,0.45,9720,,,,

,,樓梯間(帶前室),,16200,0.018,6,0,0.00,3.2,0.70,2,4.48,,,,16200,0.30,0.90,19440,,表5.1.1-1消防電梯前室的加壓送風(fēng)量,,

,,樓梯間(獨(dú)立),,29300,0.031,12,4,0.44,3.8,1.00,2,7.68,,,,29300,0.54,1.63,35160,,系統(tǒng)負(fù)擔(dān)高度h(m),加壓送風(fēng)量(m3/h),

,2,合用前室(1個(gè)門(mén)),16200,,,,,,3.2,0.70,2,4.48,0.45,0,0.00,16200,0.30,0.45,19440,,24≤h<50,"13,800~15,700",

,,樓梯間(帶前室),,16200,0.018,6,0,0.00,3.2,0.70,2,4.48,,,,16200,0.30,0.45,19440,,50≤h<100,"16,000~20,000",

,,樓梯間(獨(dú)立),,40000,0.031,12,4,0.44,3.8,0.70,4,10.64,,,,40000,0.74,1.11,48000,,,,

,3,合用前室(1個(gè)門(mén)),24200,,,,,,3.2,0.70,3,6.72,0.45,0,0.00,24200,0.45,0.45,29040,,表5.1.1-2樓梯間自然通風(fēng),前室、合用前室的加壓送風(fēng)量,,

,,樓梯間(帶前室),,16300,0.018,6,1,0.05,3.2,0.70,2,4.48,,,,16300,0.30,0.30,19560,,系統(tǒng)負(fù)擔(dān)高度h(m),加壓送風(fēng)量(m3/h),

,,樓梯間(獨(dú)立),,16300,0.018,6,1,0.05,3.2,0.70,2,4.48,,,,16300,0.30,0.30,19560,,24<h≤50,"16,300~18,100",

,6,合用前室(1個(gè)門(mén)),24700,,,,,,3.2,0.70,3,6.72,0.46,3,0.11,24700,0.46,0.46,29640,,50<h≤100,"18,400~22,000",

,,樓梯間(帶前室),,16800,0.018,6,4,0.18,3.2,0.70,2,4.48,,,,16800,0.31,0.47,20160,,,,

,,樓梯間(獨(dú)立),,16800,0.018,6,4,0.18,3.2,0.70,2,4.48,,,,16800,0.31,0.47,20160,,表5.1.1-3前室不送風(fēng),封閉樓梯間、防煙樓梯間的樓梯間加壓送風(fēng)量,,

,8,合用前室(1個(gè)門(mén)),24900,,,,,,3.2,0.70,3,6.72,0.46,5,0.19,24900,0.46,0.46,29880,,系統(tǒng)負(fù)擔(dān)高度h(m),加壓送風(fēng)量(m3/h),

,,樓梯間(帶前室),,17200,0.018,6,6,0.27,3.2,0.70,2,4.48,,,,17200,0.32,0.32,20640,,24<h≤50,"25,400~28,700",

,,樓梯間(獨(dú)立),,17200,0.018,6,6,0.27,3.2,0.70,2,4.48,,,,17200,0.32,0.32,20640,,50<h≤100,"40,000~46,400",

,12,合用前室(1個(gè)門(mén)),25200,,,,,,3.2,0.70,3,6.72,0.35,9,0.26,25200,0.47,0.35,30240,,,,

,,樓梯間(帶前室),,26300,0.018,12,9,0.58,3.2,0.70,3,6.72,,,,26300,0.49,0.49,31560,,表5.1.1-4防煙樓梯間的樓梯間及合用前室的分別加壓送風(fēng)量,,

,,樓梯間(獨(dú)立),,26300,0.018,12,9,0.58,3.2,0.70,3,6.72,,,,26300,0.49,0.37,31560,,系統(tǒng)負(fù)擔(dān)高度h(m),送風(fēng)部位,加壓送風(fēng)量(m3/h)

,18,合用前室(1個(gè)門(mén)),26400,,,,,,3.2,0.70,3,6.72,0.49,15,0.61,26400,0.49,0.49,31680,,24<h≤50,樓梯間,"17,800~20,200"

,,樓梯間(帶前室),,26700,0.018,6,15,0.68,3.2,0.70,3,6.72,,,,26700,0.49,0.25,32040,,,合用前室,"10,200~12,000"

,,樓梯間(獨(dú)立),,26700,0.018,6,15,0.68,3.2,0.70,3,6.72,,,,26700,0.49,0.25,32040,,50<h≤100,樓梯間,"28,200~32,600"

,20,合用前室(1個(gè)門(mén)),26800,,,,,,3.2,0.70,3,6.72,0.50,17,0.71,26800,0.50,0.50,32160,,,合用前室,"12,300~15,800"

,,樓梯間(帶前室),,27000,0.018,6,17,0.77,3.2,0.70,3,6.72,,,,27000,0.50,0.21,32400,,,,

,,樓梯間(獨(dú)立),,27000,0.018,6,17,0.77,3.2,0.70,3,6.72,,,,27000,0.50,0.21,32400,,注:1表5.1.1-1至表5.1.1-4的風(fēng)量按開(kāi)啟2.0m×1.6m的雙扇門(mén)確定。當(dāng)采用單扇門(mén)時(shí),,,

,24,合用前室(1個(gè)門(mén)),27400,,,,,,3.2,0.70,3,6.72,0.51,21,0.89,27400,0.51,0.51,32880,,"其風(fēng)量可乘以0.75系數(shù)計(jì)算,當(dāng)設(shè)有多個(gè)疏散門(mén)時(shí),其風(fēng)量應(yīng)乘以開(kāi)啟疏散門(mén)的數(shù)量,最",,

,,樓梯間(帶前室),,27700,0.018,6,21,0.96,3.2,0.70,3,6.72,,,,27700,0.51,0.19,33240,,多按3扇疏散門(mén)開(kāi)啟計(jì)算;,,

,,樓梯間(獨(dú)立),,27700,0.018,6,21,0.96,3.2,0.70,3,6.72,,,,27700,0.51,0.19,33240,,2表5.1.1-1至表5.1.1-4中未考慮防火分區(qū)跨越樓層時(shí)的情況;當(dāng)防火分區(qū)跨越樓層時(shí)應(yīng)按照本規(guī)范公式5.1.4~公式5.1.7重新計(jì)算;,,

,26,合用前室(1個(gè)門(mén)),27700,,,,,,3.2,0.70,3,6.72,0.51,23,0.97,27700,0.51,0.51,33240,,3表中風(fēng)量的選取應(yīng)按建筑高度或?qū)訑?shù)、風(fēng)道材料、防火門(mén)漏風(fēng)量等因素綜合確定。,,

,,樓梯間(帶前室),,28000,0.018,6,23,1.05,3.2,0.70,3,6.72,,,,28000,0.52,0.17,33600,,,,

,,樓梯間(獨(dú)立),,28000,0.018,6,23,1.05,3.2,0.70,3,6.72,,,,28000,0.52,0.17,33600,,,,

,28,合用前室(1個(gè)門(mén)),28100,,,,,,3.2,0.70,3,6.72,0.52,25,1.

溫馨提示

  • 1. 本站所有資源如無(wú)特殊說(shuō)明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁(yè)內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒(méi)有圖紙預(yù)覽就沒(méi)有圖紙。
  • 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
  • 5. 人人文庫(kù)網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
  • 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
  • 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。

最新文檔

評(píng)論

0/150

提交評(píng)論