版權說明:本文檔由用戶提供并上傳,收益歸屬內容提供方,若內容存在侵權,請進行舉報或認領
文檔簡介
ICS
29.240.99CCS
F
DB43湖 南 省 地 方 標 準DB43/T
192021數字化電能計量裝置整體誤差檢測技術規(guī)范Entirety
error
inspection
specifications
of
digitalelectric
energy
metering
devices2021-02-20
2021-05-20
湖南省市場監(jiān)督管理局
DB43/T
1997— 前言························································································································
Ⅲ1 ·····················································································································12 規(guī)范性引用文件······································································································13 術語和定義············································································································14 縮略語··················································································································25 技術要求···············································································································25.1數字化電能表工作誤差·······················································································25.2 模擬量輸入合并單元工作誤差
··············································································25.3 電子式互感器工作誤差·······················································································25.4 數字化電能計量裝置整體誤差
··············································································35.5 總電能示值組合誤差··························································································
45.6 數字化電能表時鐘示值偏差
·················································································46 檢測設備與條件······································································································46.1 檢測設備要求···································································································46.2 檢測條件·········································································································57 檢測內容與方法······································································································57.1 檢測項目·········································································································57.2 檢測方法·········································································································5附錄
A(資料性附錄) 誤差限制計算范例·······································································8附錄
B(資料性附錄) 誤差檢驗原始記錄·······································································9DB43/T
1997— 本文件按照
GB/T
—
給出的規(guī)則起草。請注意本文件的某些內容可能涉及專利,本文件的發(fā)布機構不承擔識別專利的責任。本文件由湖南省市場監(jiān)督管理局提出并歸口。陽供電分公司王紅亮、易明、趙迎慶。IIIDB43/T
1997—1
本文件規(guī)定了
50Hz
或
求、檢驗方法及檢驗結果的處理。本文件適用于數字化電能計量裝置的整體誤差檢驗工作。2
規(guī)范性引用文件文件。GB/T
17215.303—2013 交流電測量設備特殊要求第
3
部分:數字化電能表GB/T
—2007 互感器第
7
部分:電子式電壓互感器GB/T
—2007 互感器第
8
部分:電子式電流互感器DL/T
—2012合并單元測試規(guī)范DL/T
—2012 合并單元技術條件DL/T
變電站通信網絡和系統(tǒng)第
9-1
部分:特定通信服務影射(SCSM)-通過單向多路點對點串行通信鏈路的采樣值-DL/T
變電站通信網絡和系統(tǒng)第
9-2
SCSM)
IS0/IEC8802-3-的采樣值DL/T
1394—2014 電子式電流、電壓互感器檢測裝置技術條件DL/T
1664—2016電能計量裝置現場檢驗規(guī)程DL/T
1665—2016數字化電能計量裝置現場檢測規(guī)范3
術語和定義GB/T
17215.303—2013、GB/T
—2007、GB/T
20840.8—2007、DL/T
—2012界定的以及下列術語和定義適用于本文件。3.1數字化電能計量裝置
electric
energy
device合并單元,以及連接他們的數字化傳輸回路組成的用于電能計量的裝置。3.2模擬量輸入合并單元
unit
with
analogue
具備交流電壓、交流電流模擬量輸入通道的合并單元。3.3電子式互感器
instrument
transformerDB43/T
1997—用一臺合并單元完成此功能。[GB/T
20840.8—2007
3.1.1]3.4比值誤差 ratio
電子式互感器測量電流/電壓時出現的誤差,它由于實際變比不等于額定變比而產生。[GB/T20840.8—2007,定義
3.5相位差 phase
弧表示。對數字量輸出,為一次端子某一電流的出現瞬時與所對應數字數據集在
MU
輸出的傳輸起始瞬時之時間差(用額定頻率的角度單位表示)。[GB/T
20840.8—2007,
3.1.26]3.6相位誤差 phase
等于相位差減去由額定相位偏移和額定延遲時間構成的相位移。相位誤差是對額定頻率而言。由于數字量輸出要求與時鐘脈沖同步,相位誤差是時鐘脈沖與數字量傳輸值對應的一次電壓/相位誤差通常用分或厘弧表示。[GB/T
—
4
縮略語下列縮略語適用于本文件。ASDU:應用服務數據單元(Application
Service
Data
Unit)APPID:應用標識符(ApplicationIdentifier)MAC:媒體訪問控制(
Access
)MU:合并單元(Merging
Unit):每秒脈沖(
Per
Second)SVID:采樣值標識符(
Value
Identifier)5
技術要求5.1 數字化電能表工作誤差數字化電能表的工作誤差應滿足
GB/T
17215.303—2013、DL/T
1665—2016
中技術要求。5.2 模擬量輸入合并單元工作誤差模擬量輸入合并單元的電流、電壓通道比值誤差和相位誤差應滿足
DL/T
282—2012、DL/T
1665—2016
中技術要求。5.3 電子式互感器工作誤差 ) )
) + )
) ) )
) + )
) U I U I U I ( )
U ) ) ) U U ??(2) sin(
)
U I ) )
) + )
) U I U I U I ( )
U Wh ) ) ) U U
?(4) sin(
)
U I I
??(1) I
?(3)電子式電流互感器比值誤差和相位誤差應滿足
GB/T
20840.8—2007、DL/T
1665—2016
中技術要求;電子式電壓互感器比值誤差和相位誤差應滿足
GB/T
20840.7—2007、DL/T
—2016
中技術要求。5.4 數字化電能計量裝置整體誤差全數字化電能計量裝置整體的有功測量相對誤差應不超過式(1)的規(guī)定; 無功測量相對誤差應不超過式(2)的規(guī)定。 I
)
)sin(
+U
II
sin( 式(1)、(2)中:ε——數字化電能計量裝置整體的相對誤差;MAX{X}——變量
X
的最大值;ε
——數字化電能表相對誤差;N ——數字化電能計量裝置測量對象的相別數;U ——實際工作電壓;I ——實際工作電流;θ ——基波波形的功率因數角;Uf——電子式電壓互感器比差;If ——電子式電流互感器比差;Uδ——電子式電壓互感器角差;Iδ ——電子式電流互感器角差。前端配置傳統(tǒng)互感器的數字化電能計量裝置整體的有功相對誤差應不超過式(3)的規(guī)定; 無功相對誤差應不超過式(4)的規(guī)定。 I
)
)sin(
U
II
sin( 式(3)、(4)中:ε ——數字化電能計量裝置整體的相對誤差;MAX{X}——變量
X
的最大值;ε
——數字化電能表相對誤差;N——數字化電能計量裝置測量對象的相別數;DB43/T
1997—U ——實際工作電壓;I ——實際工作電流;I ——基波波形的功率因數角;UM ——電壓合并單元比差;IM ——電流合并單元比差;Uδ——電壓合并單元角差;Iδ——電流合并單元角差。上述
IfIδ
應符合
GB/T
17215.303—2013、GB/T
—2007、GB/T
20840.8—2007、DL/T
—2012、
1665—2016、DL/T
—2016
對數字化電能值的計算范例見附錄
A5.5 總電能示值組合誤差對于分時計量的電能表,計數器示值的組合誤差應符合式(5)的規(guī)定。WD
-
WD1
WD2
WDn
n110
?????????????(5)式中:WD ——當前電子顯示器總電能計數器的電能量;D1,D2,?,Dn——當前各費率時段對應的計數器的電能量;n——費率數;α ——電子顯示總電能計數器小數位數。5.6 數字化電能表時鐘示值偏差數字化電能表的時鐘示值誤差限應不超過±5min。6
檢測設備與條件6.1 檢測設備要求進行數字化電能計量裝置整體誤差檢測時,應滿足以下條件:a)
電能表檢測裝置至少應比被檢數字化電能表高兩個準確度等級;b)
標準感器高兩個準確度等級,在現場檢驗環(huán)境條件下的實際誤差不大于被檢電子式電流互感器基本誤差限值的
1/5;c)
實際誤差不大于被檢電子式電壓互感器基本誤差限值的
;d)
標準電流/電壓互感器的二次實際負荷應在其額定負荷與下限負荷之間。e)
檢測時,監(jiān)視用電流、電壓表的準確度等級應在
1.5
級以上,在同一量程的所有示值范圍內,電流、電壓表的內阻抗應保持不變;f)
光電采樣器的技術要求應滿足
DL/T
1664—;g)
升壓設備由調壓器、升壓器(高壓試驗變壓器或串聯(lián)諧振升壓裝置)等組成,升流設備由調器相適應;c
a
b
DB43/T
1997—6.2 檢測條件數字化電能計量裝置整體誤差檢測時,應滿足以下條件:a)
環(huán)境溫度:-25℃~+55℃;b)
相對濕度:≤95%;c)
頻率:50Hz±0.5Hz;d)
負荷波動:≤5%;e)
電壓對額定電壓的偏差不超過±5f)
電壓和電流的波形失真度:≤5%;g)
用于檢測工作的配套設備,如升壓器、升流器、調壓器、大電流電纜線、電壓回路壓降等接線所引起的測量誤差,不應大于被檢數字化電能計量裝置誤差限值的
1/10;h)
檢測時電壓、電流的參比條件及其允許偏差應滿足
規(guī)定。7
檢測內容與方法7.1 檢測項目數字化電能表計量裝置整體誤差檢測的項目如表
1。表
1 表
1 數字化電能表計量裝置整體檢驗項目7.2.1 外觀及通電檢查目測數字化電能計量裝置外觀,應無以下缺陷:a)
外觀破損、潮濕,有放電痕跡;b)
無銘牌及銘牌信息不全;c)
端鈕缺失、損壞、無標識;d)
基本按鍵功能不正常;e)
影響檢測工作的其他缺陷。7.2.2 參數配置檢查核查數字化電能表與對應的合并單元的參數配置是否一致,數字化電能表的運行狀態(tài)是否正常。cosθ=1
asinθ
cosθcosθsinθ
sinθ
C)b1.2In
In
In
In1.2
InIn10
In
In1.2
InIn
In
In1.2
InIn10
In
InIn
InDB43/T
1997—7.2.3 基本誤差測量
2
所示。方式,主要分為全數字化電能計量配置、經傳統(tǒng)互感器接入的數字化電能計量配置兩種。表
2 表
2 數字化電能計量裝置整體基本誤差測量負載點
1輸出脈沖,電能表檢測裝置計算數字化電能計量裝置整體誤差。
圖
1全數字化電能計量配置的整體誤差檢測接線對于已經投運的全數字化電能計量裝置,不宜開展實負荷下的整體誤差檢測。7.2.3.2 經傳統(tǒng)互感器接入的數字化電能計量配置2。使用三相可調功率源,產生相位可調的三相電壓和電流,輸出至模擬量輸入合并單元、電能表檢測0.05
0.1
0.2S
0.5S
0.0050.010.020.05DB43/T
1997—裝置,脈沖采集器獲取數字化電能表輸出脈沖,電能表檢測裝置計算數字化電能計量裝置整體誤差。三相電壓輸出三相可調功率源三相電流輸出
電壓合并單元電流合并單元
數字信號傳輸環(huán)節(jié)數字信號傳輸環(huán)節(jié)
數字化電能表電能脈沖電能誤差計算器電能脈沖標準電能表電能表檢測裝置圖
2 經傳統(tǒng)互感器接入的數字化電能計量配置的虛負荷法誤差檢測接線
3能表輸出脈沖,電能表檢測裝置計算數字化電能計量裝置整體誤差。傳統(tǒng)電壓互感器電壓合并單元
數字信號傳輸環(huán)節(jié)數字信號傳輸環(huán)節(jié)
數字化電能表電能脈沖電能誤差計算器傳統(tǒng)電流互感器
電能脈沖二次電流電流合并單元
標準電能表電能表檢測裝置圖
3 經傳統(tǒng)互感器接入的數字化電能計量配置的實負荷法誤差檢測接線7.2.4 檢驗結果處理7.2.4.1 誤差修約按表
3
規(guī)定,誤差檢驗數據以數字化電能表相應等級修約。表
3 表
3 檢測誤差修約間距檢驗結束,由檢驗單位給出檢驗結論,出具檢驗報告。檢驗原始記錄格式參見附錄表
B。
dc
InIIncos±1.15InI
In±0.7520
InI≤120%
In±0.60InI
In0.8±3.49InI
In0.8±2.3210InI20
In0.8±2.1220
InI≤120%
In0.8±1.71InI
In0.5±2.33InI
In0.5±1.6010InI20
In0.5±1.4020
InI≤120%
In0.5±1.14InI
Insinθ
3.48InI
In2.5620
InI≤120%
In2.41InI
In0.54.3610InI20
In0.53.8520
InI≤
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網頁內容里面會有圖紙預覽,若沒有圖紙預覽就沒有圖紙。
- 4. 未經權益所有人同意不得將文件中的內容挪作商業(yè)或盈利用途。
- 5. 人人文庫網僅提供信息存儲空間,僅對用戶上傳內容的表現方式做保護處理,對用戶上傳分享的文檔內容本身不做任何修改或編輯,并不能對任何下載內容負責。
- 6. 下載文件中如有侵權或不適當內容,請與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準確性、安全性和完整性, 同時也不承擔用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。
最新文檔
- 生物標志物在藥物臨床試驗中的生物標志物策略
- 生物制品穩(wěn)定性試驗文檔規(guī)范與完整性
- 生物制劑失應答后IBD的聯(lián)合治療策略-1
- 生物3D打印器官供應鏈管理策略
- 內控主管筆試題及解析
- 深度解析(2026)《GBT 19569-2004潔凈手術室用空氣調節(jié)機組》
- 生活方式干預習慣優(yōu)化方案
- 體育產業(yè)資料員招聘面試問題集
- 日化產品銷售數據分析技巧面試題
- 深度解析(2026)《GBT 19320-2003小艇 汽油發(fā)動機逆火火焰控制》
- 感術行動培訓課件
- DB44∕T 2552-2024 藥物臨床試驗倫理審查規(guī)范
- 跨區(qū)域文化協(xié)作-洞察及研究
- 2025 易凱資本中國健康產業(yè)白皮書 -生物制造篇(與茅臺基金聯(lián)合發(fā)布)
- 產業(yè)經濟學(蘇東坡版)課后習題及答案
- T/CECS 10227-2022綠色建材評價屋面綠化材料
- 區(qū)域醫(yī)學檢驗中心項目建設方案
- 小學四年級安全教育上冊教學計劃小學四年級安全教育教案
- 個人優(yōu)勢與劣勢分析
- VCR接頭鎖緊工作程序
- 2025閥門裝配工藝規(guī)程
評論
0/150
提交評論